AMP DRAW BASED ON HORSEPOWER
| HP | 1 Phase Amps | |
|---|---|---|
| 115 volt | 230 volt | |
| 1/2 | 9.8 | 4.9 |
| 3/4 | 13.8 | 6.9 |
| 1 | 16 | 8 |
How many amps does a 3 HP 480 volt motor draw?
AC Motor Full Load Amperes
| HP | 200 Volts | 440-480 Volts |
|---|---|---|
| 2 | 7.8 | 3.4 |
| 3 | 11 | 4.8 |
| 5 | 17.5 | 7.6 |
| 7.5 | 25.3 | 11 |
How many amps does a 300 hp motor draw?
Here are the Full Load Amp (FLA) values for typical 230VAC and 480VAC 3 phase motors.
| Motor horsepower | Full load amps 230VAC | Full load amps 460VAC |
|---|---|---|
| 150 | 360 | 180 |
| 200 | 480 | 240 |
| 250 | 580 | 290 |
| 300 | 696 | 348 |
How many horsepower is a 7 amp motor?
Common Amps to Horsepower Conversions
| Amps | Horsepower | Voltage |
|---|---|---|
| 4 A | .58 HP | 120 V |
| 5 A | .72 HP | 120 V |
| 6 A | .87 HP | 120 V |
| 7 A | 1.01 HP | 120 V |
How many amps does a 1 hp 120v motor draw?
Common Horsepower to Amps Conversions
| Horsepower | Amps | Voltage |
|---|---|---|
| .5 HP | 3.45 A | 120 V |
| .75 HP | 5.18 A | 120 V |
| 1 HP | 6.91 A | 120 V |
| 1.25 HP | 8.63 A | 120 V |
What size breaker do I need for a 30 hp motor?
Full-Load Current and Circuit Protection Data for Three-Phase AC Motors
| Motor Horsepower | Breaker Size | |
|---|---|---|
| 25 | 230 V 460 V | 100 50 |
| 30 | 230 V 460 V | 125 70 |
| 40 | 230 V 460 V | 175 100 |
| 50 | 230 V 460 V | 200 150 |
What size breaker do I need for a 20 hp motor?
Full Load Current: Three Phase AC Motors
| Motor Horsepower | Size Breaker | |
|---|---|---|
| 7-1/2 | 230V 460V | 40 30 |
| 10 | 230V 460V | 50 30 |
| 15 | 230V 460V | 70 40 |
| 20 | 230V 460V | 100 50 |
How many amps does a 5.5 kW motor draw?
Three Phase Motors
| MOTOR RATING | HP | APPROX. F.L.C. AT LINE VOLTAGE |
|---|---|---|
| 4.0 kW | 5.5 | 16 |
| 5.5 kW | 7.5 | 20 |
| 7.5 kW | 10 | 27 |
| 9.3 kW | 12.5 | 34 |
Can a 230V motor run on 110v?
220v and 110v systems are compatible, they just need a voltage converter. While most of the world uses 220-volt electricity, the United States uses a combination of 220v and 110v appliances. It is possible to use a 220v machine on a 110v line, however; all you need is a voltage converter.